"Allow 60 watts per square metre." Installers have used this rule for decades, and for an older house it was not a bad guess. For a new, well-insulated prefab house it usually doubles the answer. The house in our example below needs about 4 kW on the coldest night of the year. The floor-area rule says 8.4 kW. The bigger unit costs more and runs worse for most of the winter.
Heat demand is a property of the building, not of its size
A house loses heat in two ways: through the envelope (walls, roof, floor, windows and the junctions between them) and through air that leaves it. Both can be expressed as one number, the heat loss coefficient H, in watts per kelvin. Multiply it by the difference between the indoor temperature and the design outdoor temperature and you have the peak heat load:
P = H × (θint − θe)
This is the core of the method in EN 12831-1, the European standard for heat load calculation. Floor area enters only indirectly, through the size of the surfaces. Two houses of 140 m² can have heat loss coefficients that differ by a factor of three.
Worked example: a 140 m² single-storey house
We take a house with U-values close to the Norwegian TEK17 energy measures (§ 14-2) and a 0.16 wall of the kind we calculated in our article on wall U-values. The areas are simplified, and the factors marked as indicative are typical values, not figures from a specific design.
- external walls, 130 m² net × 0.16 = 20.8 W/K
- roof, 140 m² × 0.12 = 16.8 W/K
- slab on ground, 140 m² × 0.12, reduced by about half because the ground is warmer than the outside air in winter (indicative) = 8.4 W/K
- windows and doors, 25 m² × 0.80 = 20.0 W/K
- thermal bridges, 0.05 W/K per m² of heated floor (the TEK17 small-house figure) × 140 = 7.0 W/K
The envelope adds up to about 73 W/K. Now the air. TEK17 asks for a ventilation rate of 1.2 m³/h per m² of floor, so 168 m³/h here. Air carries 0.34 Wh per cubic metre per kelvin, which gives 57 W/K without heat recovery. A heat recovery unit with 80 % efficiency leaves 11.4 W/K. Leakage through the envelope comes on top: with a tested n50 of 1.5 air changes per hour, a common rule of thumb puts natural infiltration at about one twentieth of that, which is roughly 9 W/K for a house of 364 m³.
H ≈ 73 + 11.4 + 9.3 ≈ 94 W/K
At 21 °C inside and −20 °C outside the difference is 41 K:
P ≈ 94 × 41 ≈ 3.85 kW
The 60 W/m² rule gives 140 × 60 = 8.4 kW. Without heat recovery it would be about 5.7 kW: in a modern house much of the load is air, not walls.
The design temperature decides more than people expect
The −20 °C above is a typical inland value for southern Norway or eastern Poland, where the Polish national annex to EN 12831 uses zones from −16 °C on the coast to −24 °C in the north-east. Near London the design temperature is close to −2 °C. The same house there needs 94 × 23 ≈ 2.2 kW. Use the published value for your location; these figures are indicative and change as climate data is updated.
Annual energy is a different question from peak power. In a climate with roughly 4,000 heating degree-days a year, which is a fair indicative figure for the Oslo region, gross heat demand is 94 × 4,000 × 24 / 1,000 ≈ 9,000 kWh. Sun and internal gains from people and appliances cover part of it. At a seasonal performance factor of 3.5 the electricity for space heating lands somewhere around 2,000–2,600 kWh a year.
Why the bigger unit is worse, not safer
An inverter heat pump can turn itself down, but only so far. Many units cannot go much below a quarter or a third of their rated output (check the data sheet; it varies widely). The coldest night is rare. Most of the season sits between 0 °C and +8 °C, where our house needs 1.2–2 kW.
- A unit sized at about 4 kW modulates down to 1–1.5 kW and runs in long, steady cycles.
- An 8 kW unit with a minimum of 2.5–3 kW produces more than the house can take. It switches on, overheats the water, switches off and starts again a few minutes later.
Short cycling wears the compressor and lowers seasonal efficiency. The SCOP printed on the label, measured under EN 14825, assumes the unit is running in its proper range. An oversized unit rarely gets there.
Flow temperature matters as much as kW
A heat pump works more efficiently the smaller the lift between the outdoor air and the water it delivers. Underfloor heating in a well-insulated house runs at 30–35 °C on a cold day. Radiators sized for an old boiler may need 50–55 °C. A common rule of thumb is 2–3 % better efficiency for every kelvin lower flow temperature. Going from 55 °C to 35 °C is worth far more than any difference between two brands.
A concrete slab with underfloor pipes also stores a lot of heat. In many low-energy houses that thermal mass does the job a buffer tank used to do. Some manufacturers still require a minimum water volume for defrosting, so follow the installation manual, but a large buffer added "just in case" is usually unnecessary.
What really matters when you choose a heat pump
- A room-by-room heat load calculation to EN 12831-1, based on the actual U-values, the measured or specified airtightness and the ventilation system.
- The local design temperature, taken from the national annex or the local authority, not a round number.
- Output at the design temperature, not the rated output. Air-source units deliver less as it gets colder, and the data sheet shows by how much.
- Minimum modulation, compared with the heat load at 0 to +5 °C.
- Hot water as a separate item. Four people use roughly 10 kWh of hot water heat a day. A storage cylinder with a priority hour covers this without sizing the whole system up.
Does the frame material change the result?
Not by itself. A light-steel house and a C24 timber-frame house with the same U-values, the same thermal bridge allowance and the same airtightness have the same H. The difference is in how those values are reached: steel needs continuous insulation outside the frame, because it conducts heat far better than timber. Once that is designed in, the heat pump does not know what the walls are made of. Frost and moisture during assembly are a separate topic, covered in our article on building in winter.
Frequently asked questions
Should I add a safety margin?
A small one, for heating up after a holiday or for hot water, is reasonable. Doubling the calculated load is not. The design temperature is already a rare, cold value.
What about the electric backup heater?
Most units have one. In a correctly sized system it should run for a few hours a year at most, on the very coldest days or during defrost. If it runs often, the heat pump is too small or the flow temperature is too high.
Can I size the heat pump before the house is finished?
Yes, from the design U-values and the ventilation plan. The airtightness test after completion confirms the assumption.
In short
Peak heat demand is H × ΔT. For a 140 m² prefab house with good walls and heat recovery that is about 4 kW at −20 °C, roughly half of what the floor-area rule suggests. Size for that, keep the flow temperature low and the heat pump will run in long, quiet cycles. Every VDOM24 house is produced in Poland, as a C24 timber frame or a light-steel frame on one and the same floor plan. Find out more about the houses and our Norwegian partners, or ask us about your project.