"In the North you need thick walls." People say it about log houses, about masonry and about prefab homes alike, and they usually mean it as a measure of quality: the more centimetres, the warmer the house. Thickness on its own tells you very little. A 60 cm wall of aerated concrete and a 21 cm layer of mineral wool can lose exactly the same amount of heat. The number that does matter is the U-value, and once you understand how it is calculated, the question "how thick?" becomes "thick with what?".
What a U-value is, in one sentence
The U-value is the number of watts that pass through one square metre of wall for every degree of temperature difference between inside and outside. A wall with U = 0.16 W/m²K loses 0.16 W per square metre per kelvin. On a −20 °C night with 20 °C indoors, the difference is 40 K, so each square metre leaks 0.16 × 40 = 6.4 W. Lower is better, and the scale is not linear in comfort or cost, as we will see below.
What the building regulations ask for
Three regulations are relevant to most of our customers. The figures below are the published maximum values for new homes; always check the current text before using them for a design.
- Norway, TEK17 (dibk.no). The energy measures route in § 14-2 sets external walls at 0.18 W/m²K, roofs at 0.13, floors at 0.10 and windows at 0.80. The absolute minimum in § 14-3, which applies whichever route you choose, is 0.22 for walls.
- Poland, Technical Conditions (WT 2021). External walls 0.20 W/m²K, roofs 0.15, ground floors 0.30, vertical windows 0.9.
- England, Approved Document L (2021). Limiting values for new dwellings are 0.26 for walls, 0.16 for roofs, 0.18 for floors and 1.6 for windows. Compliance is shown against a "notional dwelling" that uses a 0.18 wall, so in practice designers aim much lower than 0.26.
Sweden and Finland regulate mainly through whole-building energy figures, so their wall values come out of a calculation rather than a single table entry. Across all of these, a wall around 0.16 W/m²K sits comfortably inside the strictest common limit in Norway.
Why thickness is the wrong unit
Each layer of a wall resists heat flow according to its thickness divided by its thermal conductivity, λ (lambda). The EN ISO 6946 method simply adds those resistances, plus fixed surface resistances of 0.13 m²K/W inside and, for a ventilated façade, the same again outside:
R = d / λ U = 1 / (Rsi + ΣR + Rse)
To reach U = 0.16, the total resistance must be 1 / 0.16 = 6.25 m²K/W. Take away the two surface resistances and the materials have to supply about 5.99 m²K/W. Here is how much of a single material that takes, using typical λ values (indicative, real products vary):
- PIR board, λ 0.022: about 13 cm
- mineral wool, λ 0.035: about 21 cm
- wood fibre board, λ 0.040: about 24 cm
- aerated concrete block, λ 0.10: about 60 cm
- solid softwood, λ 0.13: about 78 cm
- reinforced concrete, λ around 2.0: about 12 m
The same thermal result spans a factor of almost a hundred in thickness. A "thick" wall can be a poor one, and a slim wall can be an excellent one. What you are buying is resistance, not centimetres.
A worked example: a 0.16 timber-frame wall
Real walls are not homogeneous. Studs interrupt the insulation, and EN ISO 6946 deals with this by calculating an upper and a lower limit of resistance and averaging them. Our example is a timber-frame wall, from inside out, with studs taking about 12 % of the area:
- plasterboard 12.5 mm: 0.05
- service layer, 45 mm mineral wool: 1.29
- OSB 15 mm (also the airtight and vapour-control layer): 0.12
- C24 studs 145 mm with mineral wool between: 4.14 through the wool, 1.12 through the timber
- wood fibre sheathing 60 mm: 1.50
- ventilated cavity and cladding: counted as a surface resistance of 0.13
Treating the two paths in parallel gives an upper limit of 6.78 m²K/W. Treating the stud layer as one blended layer gives a lower limit of 6.34. The standard takes the mean:
RT = (6.78 + 6.34) / 2 ≈ 6.56 m²K/W U ≈ 0.15 W/m²K
Allow a small correction for fixings and workmanship and you arrive at a realistic as-built figure of about 0.16, in a wall roughly 28–30 cm thick before cladding. Notice how much the 12 % of timber costs: without the studs the same layers would give U ≈ 0.136. That is why the external wood fibre layer and the internal service layer matter. They cover the studs with continuous insulation.
A light-steel frame follows the same logic with a sharper penalty. Steel conducts heat roughly 400 times better than softwood, so in a steel wall continuous external insulation is a requirement rather than an option. We covered how frost affects both materials in our article on winter assembly.
What the difference is worth
Take a detached house with 140 m² of external wall. Compare a wall built to the English limit of 0.26 with one at 0.16:
(0.26 − 0.16) × 140 m² = 14 W/K at ΔT 40 K: 560 W less peak heat demand
Over a heating season of about 4,000 degree-days (indicative for inland southern Norway or central Sweden), that is 14 × 4,000 × 24 / 1,000 ≈ 1,340 kWh a year, from the walls alone. It also lowers the peak load the heat pump has to cover, which is often the bigger saving.
Now go further, from 0.16 to 0.12. That needs about 7 cm more mineral wool and saves 0.04 × 140 = 5.6 W/K, or roughly 540 kWh a year. Going from 0.30 to 0.16 saves almost four times as much. Every extra centimetre of insulation saves less than the one before, which is why the sensible target for a Nordic home is usually somewhere between 0.12 and 0.18, not "as low as possible".
What really matters in a cold-climate wall
- A calculated U-value with the frame included. Ask for the EN ISO 6946 calculation, not the sum of the insulation thicknesses.
- Continuous insulation over the frame, either outside, inside in a service layer, or both.
- Airtightness. Leaks through joints can undo a good U-value; TEK17 limits air leakage separately for this reason.
- Junctions. Wall to slab, wall to roof and window reveals are where heat escapes; good walls with poor junctions perform like average walls.
- Moisture control. A vapour-tight warm side and a vapour-open, ventilated cold side, checked against EN ISO 13788.
Frequently asked questions
Is a lower U-value always better?
Thermally, yes, but with falling returns. Below roughly 0.12 W/m²K the money is usually better spent on windows, airtightness or ventilation with heat recovery.
Does a thicker wall mean a smaller house inside?
On a fixed footprint, yes. A 30 cm insulated frame wall gives more usable floor area than a 50–60 cm masonry wall with the same U-value, which on a typical detached house can be several square metres.
Can a light-steel wall reach the same U-value as timber?
Yes, if the steel is wrapped in continuous insulation and the U-value is calculated with the profiles included. Without that layer it cannot.
In short
A good Nordic wall is defined by its calculated U-value, not its thickness. Around 0.16 W/m²K is a solid target for Norway and well inside Polish and UK limits, and it can be reached in about 30 cm of well-designed timber frame. Our houses are built in Poland in two structures, C24 timber or light steel, with the same design in both. See how they are built, read about our partners in Norway or send us your plot and plans.